| BUS DIFFERENTIAL PROTECTION TERMINAL |
|
|
Protection Functions
- Busbar Differential system for protection of up
to 4 buses and 28 lines. Applicable to any substation scheme
- Distributed architecture
- CT saturation detectors provide a high level of stability
- External fault detector prevents trips for faults outside the
protected zone
- Dedicated elements to determine fault duration
Auxiliary Functions
- Supervisory differential unit - The main differential
element is supervised by a more sensitive differential element
that monitors the entire bus
- Differential alarm unit - These alarm elements detect differential
currents not large enough to trip the relay, but that may be an
indication of problems in the bus
- Lockout unit - Prevents the closing of breakers after a DBN
trip
- Supervisory Overcurrent unit - All trip commands are monitored
at each Bay Terminal by overcurrent elements. Trips are blocked
in those bays with a negligible current flow
- Supervisory Undervoltage unit (optional) - A bus Voltage IED
can be installed to provide additional means of fault location
detection. Trips are blocked for voltage values below the setting
value
- Breaker failure - This unit resides in the DBP units providing
indication of breaker failure for both single-pole and three-pole
trips
- Oscillography
Features
- Phase correction via virtual interposing CT software.
Allows the use of the existing transformers in retrofit applications
- Transparent communication system allows the entire substation
to be controlled from any IED
- 3 settings groups per unit
- Sequence of events log - 100 event capacity with 1 ms resolution
- Time synchronization system wide. Permits accurate analysis
of sequence of events logs
- Hardware, firmware and communications self test
- Phase current, differential current, restraint current
- Bus voltage metering (optional)
DBC
Features
- 7 digital status contact inputs (expandable to 14)
- 7 auxiliary outputs (expandable to 14)
- 13 programmable LED targets
- 2 double trip contacts
- Optional I/O modules
DBP
Features
- 8 digital status contact inputs (expandable to 16)
- 8 auxiliary outputs (expandable to 16)
- 5 programmable LED targets
- 1 double trip contact and 1 double blocking contact
- Optional I/O modules
Options
|
|
|